Functional Block: R

Types Reference: Shared types referenced below are defined in OCPP-2.1-DataTypes.md.
Types used only within this block are documented inline below.

#Messages


#GetDERControl

Direction: CSMS → CS

#GetDERControlRequest

Field Type Required Constraints Description
requestId integer Yes RequestId to be used in ReportDERControlRequest.
controlId string No maxLength: 36 Id of setting to get. When omitted all settings for controlType are retrieved.
controlType DERControlEnumType No
isDefault boolean No True: get a default DER control. False: get a scheduled control.
customData CustomDataType No
Example GetDERControlRequest
{
  "requestId": 0
}

#GetDERControlResponse

Field Type Required Constraints Description
status DERControlStatusEnumType Yes
statusInfo StatusInfoType No
customData CustomDataType No

#SetDERControl

Direction: CSMS → CS

#SetDERControlRequest

Field Type Required Constraints Description
controlId string Yes maxLength: 36 Unique id of this control, e.g. UUID
controlType DERControlEnumType Yes
isDefault boolean Yes True if this is a default DER control
curve DERCurveType No
enterService EnterServiceType No
fixedPFAbsorb FixedPFType No
fixedPFInject FixedPFType No
fixedVar FixedVarType No
freqDroop FreqDroopType No
gradient GradientType No
limitMaxDischarge LimitMaxDischargeType No
customData CustomDataType No
Example SetDERControlRequest
{
  "controlId": "string",
  "controlType": "EnterService",
  "isDefault": false
}

#SetDERControlResponse

Field Type Required Constraints Description
status DERControlStatusEnumType Yes
statusInfo StatusInfoType No
supersededIds string[] No minItems: 1, maxItems: 24 List of controlIds that are superseded as a result of setting this control.
customData CustomDataType No

#ClearDERControl

Direction: CSMS → CS

#ClearDERControlRequest

Field Type Required Constraints Description
isDefault boolean Yes True: clearing default DER controls. False: clearing scheduled controls.
controlId string No maxLength: 36 Id of control setting to clear. When omitted all settings for controlType are cleared.
controlType DERControlEnumType No
customData CustomDataType No
Example ClearDERControlRequest
{
  "isDefault": false
}

#ClearDERControlResponse

Field Type Required Constraints Description
status DERControlStatusEnumType Yes
statusInfo StatusInfoType No
customData CustomDataType No

#ReportDERControl

Direction: CS → CSMS

#ReportDERControlRequest

Field Type Required Constraints Description
requestId integer Yes RequestId from GetDERControlRequest.
curve DERCurveGetType[] No minItems: 1, maxItems: 24
enterService EnterServiceGetType[] No minItems: 1, maxItems: 24
fixedPFAbsorb FixedPFGetType[] No minItems: 1, maxItems: 24
fixedPFInject FixedPFGetType[] No minItems: 1, maxItems: 24
fixedVar FixedVarGetType[] No minItems: 1, maxItems: 24
freqDroop FreqDroopGetType[] No minItems: 1, maxItems: 24
gradient GradientGetType[] No minItems: 1, maxItems: 24
limitMaxDischarge LimitMaxDischargeGetType[] No minItems: 1, maxItems: 24
tbc boolean No To Be Continued. Default value when omitted: false. + False indicates that there are no further messages as part of this report.
customData CustomDataType No
Example ReportDERControlRequest
{
  "requestId": 0
}

#ReportDERControlResponse

No required fields. An empty {} is a valid response.


#NotifyDERAlarm

Direction: CS → CSMS

#NotifyDERAlarmRequest

Field Type Required Constraints Description
controlType DERControlEnumType Yes
timestamp string (date-time) Yes Time of start or end of alarm.
alarmEnded boolean No True when error condition has ended. Absent or false when alarm has started.
extraInfo string No maxLength: 200 Optional info provided by EV.
gridEventFault GridEventFaultEnumType No
customData CustomDataType No
Example NotifyDERAlarmRequest
{
  "controlType": "EnterService",
  "timestamp": "2024-01-15T10:30:00Z"
}

#NotifyDERAlarmResponse

No required fields. An empty {} is a valid response.


#NotifyDERStartStop

Direction: CS → CSMS

#NotifyDERStartStopRequest

Field Type Required Constraints Description
controlId string Yes maxLength: 36 Id of the started or stopped DER control. Corresponds to the controlId of the SetDERControlRequest.
started boolean Yes True if DER control has started. False if it has ended.
timestamp string (date-time) Yes Time of start or end of event.
supersededIds string[] No minItems: 1, maxItems: 24 List of controlIds that are superseded as a result of this control starting.
customData CustomDataType No
Example NotifyDERStartStopRequest
{
  "controlId": "string",
  "started": false,
  "timestamp": "2024-01-15T10:30:00Z"
}

#NotifyDERStartStopResponse

No required fields. An empty {} is a valid response.


#Local Types

Types used only within this block's messages.

#DERUnitEnumType

Unit of the Y-axis of DER curve

Value
Not_Applicable
PctMaxW
PctMaxVar
PctWAvail
PctVarAvail
PctEffectiveV

Used in: ReportDERControl, SetDERControl


#GridEventFaultEnumType

Type of grid event that caused this

Value
CurrentImbalance
LocalEmergency
LowInputPower
OverCurrent
OverFrequency
OverVoltage
PhaseRotation
RemoteEmergency
UnderFrequency
UnderVoltage
VoltageImbalance

Used in: NotifyDERAlarm


#PowerDuringCessationEnumType

Parameter is only sent, if the EV has to feed-in power or reactive power during fault-ride through (FRT) as defined by HVMomCess curve and LVMomCess curve.

Value
Active
Reactive

Used in: ReportDERControl, SetDERControl


#DERCurveGetType

Field Type Required Constraints Description
curve DERCurveType Yes
curveType DERControlEnumType Yes
id string Yes maxLength: 36 Id of DER curve
isDefault boolean Yes True if this is a default curve
isSuperseded boolean Yes True if this setting is superseded by a higher priority setting (i.e. lower value of priority)
customData CustomDataType No

Used in: ReportDERControl


#DERCurvePointsType

Field Type Required Constraints Description
x number Yes The data value of the X-axis (independent) variable, depending on the curve type.
y number Yes The data value of the Y-axis (dependent) variable, depending on the of the curve. If y is power factor, then a positive value means DER is absorbing reactive power (under-excited), a negative value when DER is injecting reactive power (over-excited).
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#DERCurveType

Field Type Required Constraints Description
curveData DERCurvePointsType[] Yes minItems: 1, maxItems: 10
priority integer Yes min: 0.0 Priority of curve (0=highest)
yUnit DERUnitEnumType Yes
duration number No Duration in seconds that this curve will be active. Only absent when default is true.
hysteresis HysteresisType No
reactivePowerParams ReactivePowerParamsType No
responseTime number No Open loop response time, the time to ramp up to 90% of the new target in response to the change in voltage, in seconds. A value of 0 is used to mean no limit. When not present, the device should follow its default behavior.
startTime string (date-time) No Point in time when this curve will become activated. Only absent when default is true.
voltageParams VoltageParamsType No
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#EnterServiceGetType

Field Type Required Constraints Description
enterService EnterServiceType Yes
id string Yes maxLength: 36 Id of setting
customData CustomDataType No

Used in: ReportDERControl


#EnterServiceType

Field Type Required Constraints Description
highFreq number Yes Enter service frequency high
highVoltage number Yes Enter service voltage high
lowFreq number Yes Enter service frequency low
lowVoltage number Yes Enter service voltage low
priority integer Yes min: 0.0 Priority of setting (0=highest)
delay number No Enter service delay
rampRate number No Enter service ramp rate in seconds
randomDelay number No Enter service randomized delay
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#FixedPFGetType

Field Type Required Constraints Description
fixedPF FixedPFType Yes
id string Yes maxLength: 36 Id of setting.
isDefault boolean Yes True if setting is a default control.
isSuperseded boolean Yes True if this setting is superseded by a lower priority setting.
customData CustomDataType No

Used in: ReportDERControl


#FixedPFType

Field Type Required Constraints Description
displacement number Yes Power factor, cos(phi), as value between 0..1.
excitation boolean Yes True when absorbing reactive power (under-excited), false when injecting reactive power (over-excited).
priority integer Yes min: 0.0 Priority of setting (0=highest)
duration number No Duration in seconds that this setting is active.
startTime string (date-time) No Time when this setting becomes active
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#FixedVarGetType

Field Type Required Constraints Description
fixedVar FixedVarType Yes
id string Yes maxLength: 36 Id of setting
isDefault boolean Yes True if setting is a default control.
isSuperseded boolean Yes True if this setting is superseded by a lower priority setting
customData CustomDataType No

Used in: ReportDERControl


#FixedVarType

Field Type Required Constraints Description
priority integer Yes min: 0.0 Priority of setting (0=highest)
setpoint number Yes The value specifies a target var output interpreted as a signed percentage (-100 to 100). A negative value refers to charging, whereas a positive one refers to discharging. The value type is determined by the unit field.
unit DERUnitEnumType Yes
duration number No Duration in seconds that this setting is active.
startTime string (date-time) No Time when this setting becomes active.
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#FreqDroopGetType

Field Type Required Constraints Description
freqDroop FreqDroopType Yes
id string Yes maxLength: 36 Id of setting
isDefault boolean Yes True if setting is a default control.
isSuperseded boolean Yes True if this setting is superseded by a higher priority setting (i.e. lower value of priority)
customData CustomDataType No

Used in: ReportDERControl


#FreqDroopType

Field Type Required Constraints Description
overDroop number Yes Over-frequency droop per unit, oFDroop
overFreq number Yes Over-frequency start of droop
priority integer Yes min: 0.0 Priority of setting (0=highest)
responseTime number Yes Open loop response time in seconds
underDroop number Yes Under-frequency droop per unit, uFDroop
underFreq number Yes Under-frequency start of droop
duration number No Duration in seconds that this setting is active
startTime string (date-time) No Time when this setting becomes active
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#GradientGetType

Field Type Required Constraints Description
gradient GradientType Yes
id string Yes maxLength: 36 Id of setting
customData CustomDataType No

Used in: ReportDERControl


#GradientType

Field Type Required Constraints Description
gradient number Yes Default ramp rate in seconds (0 if not applicable)
priority integer Yes min: 0.0 Id of setting
softGradient number Yes Soft-start ramp rate in seconds (0 if not applicable)
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#HysteresisType

Field Type Required Constraints Description
hysteresisDelay number No Delay in seconds, once grid parameter within HysteresisLow and HysteresisHigh, for the EV to return to normal operation after a grid event.
hysteresisGradient number No Set default rate of change (ramp rate %/s) for the EV to return to normal operation after a grid event
hysteresisHigh number No High value for return to normal operation after a grid event, in absolute value. This value adopts the same unit as defined by yUnit
hysteresisLow number No Low value for return to normal operation after a grid event, in absolute value. This value adopts the same unit as defined by yUnit
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#LimitMaxDischargeGetType

Field Type Required Constraints Description
id string Yes maxLength: 36 Id of setting
isDefault boolean Yes True if setting is a default control.
isSuperseded boolean Yes True if this setting is superseded by a higher priority setting (i.e. lower value of priority)
limitMaxDischarge LimitMaxDischargeType Yes
customData CustomDataType No

Used in: ReportDERControl


#LimitMaxDischargeType

Field Type Required Constraints Description
priority integer Yes min: 0.0 Priority of setting (0=highest)
duration number No Duration in seconds that this setting is active
pctMaxDischargePower number No Only for PowerMonitoring. + The value specifies a percentage (0 to 100) of the rated maximum discharge power of EV. The PowerMonitoring curve becomes active when power exceeds this percentage.
powerMonitoringMustTrip DERCurveType No
startTime string (date-time) No Time when this setting becomes active
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#ReactivePowerParamsType

Field Type Required Constraints Description
autonomousVRefEnable boolean No Only for VoltVar: Enable/disable autonomous VRef adjustment
autonomousVRefTimeConstant number No Only for VoltVar: Adjustment range for VRef time constant
vRef number No Only for VoltVar curve: The nominal ac voltage (rms) adjustment to the voltage curve points for Volt-Var curves (percentage).
customData CustomDataType No

Used in: ReportDERControl, SetDERControl


#VoltageParamsType

Field Type Required Constraints Description
hv10MinMeanTripDelay number No Time for which the voltage is allowed to stay above the 10 min mean value. After this time, the EV must trip. This value is mandatory if OverVoltageMeanValue10min is set.
hv10MinMeanValue number No EN 50549-1 chapter 4.9.3.4 Voltage threshold for the 10 min time window mean value monitoring. The 10 min mean is recalculated up to every 3 s. If the present voltage is above this threshold for more than the time defined by hv10MinMeanValue, the EV must trip. This value is mandatory if hv10MinMeanTripDelay is set.
powerDuringCessation PowerDuringCessationEnumType No
customData CustomDataType No

Used in: ReportDERControl, SetDERControl