Purpose: Practical reference for AI agents implementing or debugging OCPP 2.1 DER (Distributed Energy Resource) control — functional block R. Covers what DER control is, the control/curve model, the Get / Set / Clear / Report message flow, alarms and start/stop notifications, prioritization and superseding, and offline behavior.

Last updated: 2026-06-09


#How This Document Was Produced

This document covers OCPP 2.1 DER control (functional block R, use cases R01–R05 of the Part 2 specification). Its dominant confidence tier is spec-knowledge — behavioral rules summarized in original wording from the OCPP 2.1 Edition 2 Part 2 specification. Message names, field names, enum values, and structural constraints are schema-derived — cross-referenced against the DER Control schema reference, the data types reference, and the device model reference, all mechanically extracted from the official OCA artifacts. No spec prose is reproduced verbatim (the OCA specification is CC BY-ND licensed); all explanatory text is original.

This document contains 4 escalation points marked with > **ESCALATE:**. When an AI agent encounters one, it MUST stop and ask the developer (or grid/utility stakeholder) to make the decision. See METHODOLOGY.md for the full confidence and escalation model.

Companion documents:


#1. What DER Control Is and Why OCPP 2.1 Adds It

When a charging station (or a fleet of them) charges and discharges bidirectionally, the utility treats it as a Distributed Energy Resource (DER) — a grid-connected inverter that must obey local grid codes. Grid codes define how an inverter reacts to abnormal grid conditions: ride through a voltage sag, trip off on over-frequency, absorb or inject reactive power to support voltage, ramp slowly back into service, and so on. OCPP 2.1 adds functional block R so a CSMS can configure and observe this grid-code behavior on a charging station.

DER control also applies to charging-only stations: a utility may require frequency support (curtailing import when frequency drops) even from stations that never discharge. Throughout block R, "DER control" covers both bidirectional and charging-only cases.

#1.1 The aggregator model

OCPP does not connect a utility directly to a charging station or an EV. The flow is layered:

Step Sender → Receiver Interface Notes
1 Utility → CSMS IEC 61850 / IEEE 2030.5 / DNP3 / Modbus (out of OCPP scope) Utility sends grid-code settings, often a schedule of timed events with priorities
2 CSMS → CS OCPP block R messages CSMS, acting as the CSO/aggregator, schedules and prioritizes, then forwards the appropriate controls
3 CS → EV ISO 15118-20 (or CHAdeMO) If the inverter is in the EV, the station relays settings/targets to the EV

The CSMS carries most of the scheduling and prioritization burden. OCPP block R is the CSMS↔CS interface only.

#1.2 Relationship to ISO 15118-20 inverter architectures

Where the inverter physically lives determines who enforces the grid code. From the OCPP point of view this is irrelevant — the CSMS always sends DER controls to the charging station, which decides how to apply them.

Architecture Inverter location Who enforces grid code OCPP role
DC bidirectional (ISO 15118-20 DC_BPT, CHAdeMO) In the EVSE (charging station) The EVSE inverter directly CS applies DER controls to its own inverter
ISO 15118-20 V2G-AC (AC_BPT_DER) In the EV The EV's smart inverter CS forwards all required settings to the EV during ISO 15118-20 parameter discovery
ISO 15118-20 V2G-Split (AC_BPT_DER) Split EV + EVSE EV does what it supports; EVSE emulates the rest via ChargeLoop targets CS splits controls: EV-supported ones go to the EV, the remainder the EVSE emulates

The station reports which control modes it can emulate/enforce in the device-model variable ModesSupported (see §9). Active/reactive power setpoints and limits are not block-R messages — they are expressed as OCPP charging profiles (see Smart Charging); block R covers the grid-code behavior (curves and parameter settings) on top of those profiles.


#2. The DER Control Model

A DER control is one configured grid-code behavior. Every control has:

#2.1 Control types

The 22 values of DERControlEnumType, grouped by what they configure:

Group controlType values What it does
Enter service EnterService Voltage/frequency window and delay/ramp for (re)connecting to the grid
Frequency droop FreqDroop, FreqWatt Adjust active power as a function of frequency to stabilize the grid
Frequency trip / ride-through HFMustTrip, HFMayTrip, LFMustTrip High/low-frequency disconnect (MustTrip) and ride-through (MayTrip) curves
Voltage trip / ride-through / momentary cessation HVMustTrip, HVMayTrip, HVMomCess, LVMustTrip, LVMayTrip, LVMomCess High/low-voltage disconnect, ride-through, and momentary-cessation curves
Reactive power FixedVar, VoltVar, WattVar, FixedPFAbsorb, FixedPFInject, WattPF Fixed or curve-based reactive-power / power-factor behavior
Active power vs voltage VoltWatt Reduce/increase active power as a function of voltage
Discharge / power limits LimitMaxDischarge, PowerMonitoringMustTrip Cap discharge power; trip on a power-monitoring threshold
Ramp rates Gradients Default and soft-start ramp rates

ESCALATE: POLICY-DEPENDENT — Which control types are enabled, and the actual curve points / setpoints / thresholds inside them, are grid-code and utility-policy decisions (often per IEEE 1547, EN 50549, VDE-AR-N 4105, or a local regulator). Do not invent curve values; obtain them from the utility/CSO.

#2.2 Curves vs parameter settings

Two structural forms exist:

Form Carried in Used by Shape
Curve DERCurveType All trip/ride-through and Volt*/Watt*/FreqWatt types 1–10 (x, y) points (DERCurvePointsType), a priority, and a yUnit (DERUnitEnumType); the x-axis is frequency/voltage/power depending on type
Parameter setting type-specific object (e.g. FreqDroopType, FixedPFType, FixedVarType, EnterServiceType, GradientType, LimitMaxDischargeType) FreqDroop, FixedVar, FixedPFAbsorb, FixedPFInject, EnterService, Gradients, LimitMaxDischarge Named scalar parameters plus a priority

A frequency-droop is conceptually a parameterized Freq-Watt curve (slope + dead-band) rather than explicit points, which is why it has its own FreqDroopType object.

Curves may also carry optional refinements: HysteresisType (return-to-normal behavior after an event), VoltageParamsType (e.g. 10-minute mean over-voltage monitoring, momentary cessation via PowerDuringCessationEnumType), and ReactivePowerParamsType (VoltVar vRef / autonomous adjustment).

#2.3 controlType → payload field mapping

SetDERControlRequest carries the control-specific object in exactly one field, selected by controlType. Sending the wrong field, or more than one control, must be rejected (see §4).

controlType value(s) Required field in SetDERControlRequest
FixedPFAbsorb fixedPFAbsorb
FixedPFInject fixedPFInject
FixedVar fixedVar
LimitMaxDischarge limitMaxDischarge
FreqDroop freqDroop
EnterService enterService
Gradients gradient
all other types (trip, ride-through, VoltVar, VoltWatt, WattVar, WattPF, FreqWatt, PowerMonitoringMustTrip) curve

#2.4 Default vs scheduled controls

Two controlTypes are default-only — EnterService and Gradients. The CSMS must not send them with isDefault = false; the station rejects such a request.

Controls persist across reboots/power-cycles — the station stores them durably.


#3. Messages and Direction

Six messages make up block R. Full field-level schemas: DER Control schemas.

Message Direction Purpose
GetDERControl CSMS → CS Request installed controls matching criteria
SetDERControl CSMS → CS Install or update one DER control
ClearDERControl CSMS → CS Remove controls by id / type / default flag
ReportDERControl CS → CSMS Return controls in response to GetDERControl
NotifyDERAlarm CS → CSMS Report that a control is overriding normal behavior
NotifyDERStartStop CS → CSMS Report that a scheduled control started or stopped

All three CSMS → CS responses (Get/Set/Clear) carry a DERControlStatusEnumType status: Accepted, Rejected, NotSupported, or NotFound.


#4. Set Flow

SetDERControl installs or updates a single control. The control-specific field must match controlType (§2.3); the station rejects a request that carries multiple controls or a mismatched field.

#4.1 Setting a default control (e.g. frequency droop)

Step Sender → Receiver Message Trigger / Notes
1 Utility → CSMS (out of OCPP scope) New frequency-droop parameters arrive
2 CSMS → CS SetDERControlRequest isDefault = true, controlType = FreqDroop, freqDroop = { overFreq, underFreq, overDroop, underDroop, responseTime }, no startTime/duration
3 CS → CSMS SetDERControlResponse status = Accepted
4 CS (internal) Default droop becomes active immediately

#4.2 Setting a scheduled control (e.g. VoltVar Q(U) curve)

Step Sender → Receiver Message Trigger / Notes
1 CSMS → CS SetDERControlRequest isDefault = false, controlType = VoltVar, curve = { curveData[], priority, yUnit, startTime, duration }
2 CS → CSMS SetDERControlResponse status = Accepted
3 CS → CSMS NotifyDERStartStopRequest At startTime: controlId, started = true
4 CS (internal) For duration seconds, station adjusts reactive power per the curve
5 CS → CSMS NotifyDERStartStopRequest At startTime + duration: controlId, started = false; control then deleted

#4.3 Response rules (SetDERControlResponse)

Condition status Extra
controlType not supported by the station NotSupported
Default (isDefault=true) sent with startTime and/or duration Rejected
EnterService or Gradients sent with isDefault=false Rejected
Multiple controls, or control object not matching controlType Rejected
Valid; no existing control of this type Accepted
Valid; supersedes existing control(s) of same type Accepted supersededIds[] lists the superseded controlIds

The supersededIds array (1–24 ids) appears whenever installing this control causes others of the same type to be superseded — see §6.


#5. Get / Report and Clear Flows

#5.1 Get / Report

GetDERControl carries a requestId and optional filters (controlId, controlType, isDefault). A missing filter matches any value. The station answers the request synchronously with a GetDERControlResponse status, then streams the matching controls in one or more asynchronous ReportDERControlRequest messages (CS → CSMS), each echoing the original requestId.

Step Sender → Receiver Message Trigger / Notes
1 CSMS → CS GetDERControlRequest requestId + optional controlId / controlType / isDefault
2 CS → CSMS GetDERControlResponse status = Accepted if matches exist; see table below
3 CS → CSMS ReportDERControlRequest (1..n) Same requestId; tbc = true on every message except the last
4 CSMS → CS ReportDERControlResponse Empty {} ack for each report

GetDERControlResponse status:

Condition status
No controls match the given isDefault / controlType / controlId NotFound
controlType is one the station does not support NotSupported
One or more controls match Accepted (reports follow)

ReportDERControlRequest groups returned controls by type into arrays of "Get" wrapper types — DERCurveGetType, FreqDroopGetType, FixedPFGetType, FixedVarGetType, EnterServiceGetType, GradientGetType, LimitMaxDischargeGetType. Each wrapper adds the id (the original controlId), isDefault, and an isSuperseded flag, so the CSMS can see which installed controls are currently shadowed by a higher-priority one.

#5.2 Clear

ClearDERControl removes controls. isDefault is required (clear defaults vs scheduled); controlId and controlType are optional filters.

Step Sender → Receiver Message Trigger / Notes
1 CSMS → CS ClearDERControlRequest isDefault required; optional controlId / controlType
2 CS → CSMS ClearDERControlResponse status per table below
Condition status
controlType set + not supported by station NotSupported
controlType given but never set for that isDefault NotFound
controlId given but never set for that isDefault NotFound
No controlType/controlId → clear all controls matching isDefault Accepted
controlType matches set controls → clear them for that isDefault Accepted
controlId matches a set control → clear it for that isDefault Accepted

#6. Prioritization and Superseding

Two mechanisms decide which control of a given type is active. Type here means a specific control parameter or curve type (e.g. FreqDroop, HFMustTrip).

  1. Default vs scheduled. A scheduled control of a type, while active, overrides the default of that type. Outside any scheduled window, the default applies.
  2. priority value. Only one control of a type can be active at a time. When multiple exist, the one with the lowest priority value wins (0 = highest priority). This applies independently within defaults and within scheduled controls.

#6.1 Superseding rules

Prioritization happens when the message is received, not at start time. Key rules:

Situation Behavior
New control of a type has a lower priority value than an existing one not yet started Existing control is superseded immediately (isSuperseded = true), even if the new control starts much later
New higher-priority control arrives while a lower-priority control of the same type is already active (past startTime) Active control keeps running until the new control's startTime, then is superseded
New control has a higher priority value than an already-active control of the same type New control is accepted but immediately superseded; the existing one keeps running. Its controlId is returned in supersededIds. (The CSMS should avoid sending lower-priority controls in the first place.)
Any control with isSuperseded = true Never executed
Any control past startTime + duration Automatically deleted by the station

When no scheduled control of a type is active, the station executes the default control of that type that has isSuperseded = false.

This matches the prioritization process in the IEEE 2030.5 / CSIP profile, so a CSMS can map utility events to OCPP controls predictably. Ideally the CSMS resolves priority itself and sends only the winning control, but because network latency makes "send exactly at start time" unreliable, the station must also handle overlapping controls of differing priority.

ESCALATE: POLICY-DEPENDENT — Assigning priority values across overlapping utility events (which event group outranks another) is a CSO/utility scheduling decision. Confirm the priority scheme with the operator before relying on superseding behavior.


#7. Alarms and Start/Stop Notifications

#7.1 NotifyDERAlarm — a control overrides normal behavior

When a station starts deviating from normal (dis)charging because a DER curve or setting forced it to — for example an over-frequency causing an HFMustTrip curve to cut export — it raises a NotifyDERAlarm so the CSO is aware.

Field Use
controlType Which control took over (e.g. HFMustTrip, LimitMaxDischarge, VoltVar)
timestamp When the event started (or ended)
alarmEnded Absent/false when the alarm starts; true on the follow-up message when the condition clears
gridEventFault Optional cause, one of GridEventFaultEnumType (e.g. OverFrequency, UnderVoltage, OverCurrent, LocalEmergency)
extraInfo Optional free text (max 200), e.g. forwarded from the EV

The station sends the alarm again with alarmEnded = true when the event ends. A purely reactive-power curve (e.g. VoltVar) typically does not raise an alarm, because it does not disturb the active-power profile — unless the active charging profile also specifies reactive-power behavior.

#7.2 NotifyDERStartStop — scheduled control activation

When a scheduled control (isDefault = false, isSuperseded = false) reaches its startTime or its startTime + duration, the station reports the transition with NotifyDERStartStop.

Field Use
controlId The control that started/stopped (matches the SetDERControlRequest id)
started true at startTime, false at startTime + duration
timestamp Current time of the transition
supersededIds If starting this control supersedes others of the same type, their ids (1–24)
Trigger Message contents
Scheduled control reaches startTime started = true, controlId
...and it supersedes an active control B started = true, controlId = A, supersededIds = [B]
Scheduled control reaches startTime + duration started = false, controlId

NotifyDERAlarm and NotifyDERStartStop are distinct: start/stop reports the schedule lifecycle of a control; alarm reports that a control is actively overriding charging because of a grid event.


#8. Offline Behavior

Block R has no offline-specific messages. DER controls are stored persistently on the station, so a reboot or connectivity loss does not erase them — defaults and scheduled controls keep applying on their own timelines, and the station continues enforcing grid-code behavior autonomously (that is the point of curves: autonomous reaction without a round-trip to the CSMS).

Active/reactive power setpoints, by contrast, ride on OCPP charging profiles, whose offline lifetime is governed by maxOfflineDuration / invalidAfterOfflineDuration in ChargingProfileType (V2X use cases Q11/Q12, outside block R). See the Smart Charging deep-dive for that mechanism.

ESCALATE: SPEC-SILENT — The Part 2 DER chapter does not define a block-R-specific reconciliation procedure for what the CSMS should re-Get or re-Set after a station reconnects following a long outage (e.g. whether scheduled controls that elapsed while offline are reported as deleted). Confirm the expected reconciliation with the integration team.


#9. Device Model: DCDERCtrlr & ACDERCtrlr

DER capabilities and the set of supported control modes live in two device-model components (see the Device Model reference). Both sit at the EVSE level.

Component Represents Key variables
DCDERCtrlr DER capabilities ("nameplate") of the EVSE's own DC inverter Enabled, ModesSupported, ratings (MaxW, MaxVA, MaxVar, MaxVarNeg, MaxChargeRateW, over/under-excited W and PF), voltage ratings (VNom, MaxV, MinV), inverter identity (InverterManufacturer/Model/SerialNumber/SwVersion/HwVersion), IslandingDetectionMethod, ReactiveSusceptance
ACDERCtrlr DER modes the EVSE can emulate via ISO 15118-20 ChargeLoop to control the EV's inverter ModesSupported

ModesSupported (a MemberList) is the contract for SetDERControl/GetDERControl: the CSMS should not send (and the station will answer NotSupported for) a controlType absent from ModesSupported of the relevant controller. For a DC station the supported modes are the EVSE inverter's; for an AC station they are the modes the EVSE can emulate (the rest must be handled by the EV's inverter, per the V2G-AC / V2G-Split split in §1.2).

ESCALATE: POLICY-DEPENDENTEnabled and the contents of ModesSupported, plus all nameplate ratings, reflect hardware capability and regulatory registration of the inverter. Treat them as configuration provided by the station vendor / CSO, not values to set arbitrarily.


#10. Use Case Index

The block-R use cases (R01–R05) in the Part 2 specification map to this document as:

Use case Topic Section(s)
R01 Start V2X session with DER control in the EVSE (DC / AC emulation) §1.2, §7
R02 Start V2X session with DER control in the EV (ISO 15118-20 AC_BPT_DER) §1.2
R03 Hybrid DER control split across EV and EVSE §1.2
R04 Configure DER control settings (Set / Get / Report / Clear, start/stop) §4, §5, §6, §7
R05 / device model Reporting DER capabilities §9